WTC MUD #1 RecordsBoard minutes, agendas and votes

Past Report - 2022

Unofficial searchable copy. For the official record, use the district’s own copy.

Page 1

PWS #: 2460120
Page 1 of 4
Williamson Travis Counties MUD No. 1
2022 Drinking Water Quality Report
DEAR CUSTOMER:
This report is intended to provide you with important
information about your drinking water and the efforts
made by the water system to provide safe drinking
water.
The sources of drinking water (both tap water and
bottled water) generally include rivers, lakes, streams,
ponds, reservoirs, springs, and wells. As water travels
over the surface of the land or through the ground, it
dissolves naturally-occurring minerals, and in some
cases, radioactive material, and can pick up substances
resulting from the presence of animals or from human
activity.
Drinking water, including bottled water, may reasonably
be expected to contain at least small amounts of some
contaminants. The presence of contaminants does not
necessarily indicate that water poses a health risk. More
information about contaminants and potential health
effects can be obtained by calling the EPA’s Safe
Drinking Water Hotline (1-800-426-4791). Contaminants
that may be present in the source water include:
1) Microbial contaminants, such as viruses and bacteria,
which may come from sewage treatment plants, septic
systems, agricultural livestock operations, and 2)
Inorganic contaminants, such as salts and metals, which
can be naturally-occurring or result from urban storm
water runoff, industrial or domestic wastewater
discharges, oil and gas production, mining, or farming. 3)
Pesticides and herbicides, which may come from a
variety of sources such as agriculture, urban stormwater
runoff, and residential uses. 4) Organic chemical
contaminants, including synthetic and volatile organic
chemicals, which are by- products of industrial
processes and petroleum production, and can also,
come from gas stations, urban storm water runoff, and
septic systems. 5) Radioactive contaminants, which can
be naturally- occurring or be the result of oil and gas
production and mining production and mining activities.
In order to ensure that tap water is safe to drink, EPA
prescribes regulations which limit the amount of certain
contaminants in water provided by public water systems.
FDA regulations establish limits for contaminants in
bottled water which must provide the same protection for
public health.
Contaminants may be found in drinking water that may
cause taste, color, or odor problems. These types of
problems are not necessarily causes for health
concerns. For more information on taste, odor, or color
of drinking water, please contact the district’s operator,
Inframark.
You may be more vulnerable than the general population
to certain microbial contaminants such as
Cryptosporidium, in drinking water. Infants, some elderly,
or immunocompromised persons such as those
undergoing chemotherapy for cancer; those who have
undergone organ transplants; those who are undergoing
treatment with steroids; and people with HIV / AIDS or
other immune system disorders can be particularly at
risk from infections. You should seek advice about
drinking water from you physician or health care
provider. Additional guidelines on appropriate means to
lessen the risk of infection by Cryptosporidium are
available from the Safe Drinking Water Hotline at (800-
426-4791).
If present, elevated levels of lead can cause serious
health problems, especially for pregnant women and
young children. Lead in drinking water is primarily from
materials and components associated with service lines
and home plumbing. We are responsible for providing
high quality drinking water, but we cannot control the
variety of materials used in plumbing components. When
your water has been sitting for several hours, you can
minimize the potential for lead exposure by flushing your
tap for 30 seconds to 2 minutes before using water for
drinking or cooking. If you are concerned about lead in
your water, you may wish to have your water tested.
Information on lead in drinking water, testing methods,
and steps you can take to minimize exposure is available
from the Safe Drinking Water Hotline or at
http://www.epa.gov/safewater/lead.
The source of drinking water used by Williamson Travis
Counties MUD 1 is purchased water from the City of
Cedar Park who is providing surface water from Brushy
Creek Regional Utility Authority that comes from Lake
Travis.
TCEQ completed a Source Water Susceptibility for all
drinking water systems that own their sources. This
report describes the susceptibility and types of
constituents that may come into contact with the drinking
water source based on human activities and natural
conditions. The system(s) from which we purchase our
water received the assessment report. For more
information on source water assessments and protection
efforts at our system contact Makenzi Scales, Inframark,
at (512-457-1166).
For more information about your sources of water,
please refer to the Source Water Assessment Viewer
available at the following:
http://www.tceq.texas.gov/gis/swaview
Further details about sources and source water
assessments are available in Drinking Water Watch at
the following URL:http://dww2.tceq.texas.gov/DWW/
Many constituents (such as calcium, sodium, or iron)
which are often found in drinking water can cause taste,
color, and odor problems. The taste and odor
constituents are called secondary constituents and are
regulated by the State of Texas, not the EPA. These
constituents are not causes for health concern.
Therefore, secondaries are not required to be reported in
this document but they may greatly affect the
appearance and taste of your water. The pages that
follow list all of the federally regulated or monitored
contaminants which have been found in your drinking
water. The U.S. EPA requires water systems to test for
up to 97 contaminants.
When drinking water meets federal standards there may
not be any health based benefits to purchasing bottled
water or point of use devices.
Public input concerning the water system may be made
at regularly scheduled meetings, generally held at 6:00
PM on the 3rd Wednesday of the month at 12912 Hill
Country Blvd, Bee Cavew, TX 78738. You may also
contact Makenzi Scales, Inframark, at 512-457-1166 with
any concerns or questions you may have regarding this
report.
Este reporte incluye informacion importante sobre el
agua para tomar. Para asistencia en espanol, favor de
llamar al tel. (281) 579-4507.
Definitions & Abbreviations:
Action Level (AL): The concentration of a contaminant
which, if exceeded, triggers treatment or other requirements
which a water system must follow.
AVG: Regulatory compliance with some MCLs are based on
running annual average of monthly samples.
Level 1 assessment: Study of the water system to identify
potential problems and determine (if possible) why total
coliform bacteria have been found in our water system.
Level 2 assessment: Very detailed study of the water
system to identify potential problems and determine (if
possible) why an E. coli MCL violation has occurred and/or
why total coliform bacteria have been found in our water
system on multiple occasions.
Maximum Contaminant Level (MCL): The highest level of a
contaminant that is allowed in drinking water. MCLs are set
as close to MCLGs as feasible using the best available
treatment technology.
Maximum Contaminant Level Goal (MCLG): The level of a
contaminant in drinking water below which there is no
known or expected risk to health. MCLGs allow for a margin
of safety.
Maximum Residual Disinfectant Level (MRDL): The highest
level of disinfectant allowed in drinking water. There is
convincing evidence that addition of a disinfectant is
necessary for control of microbial contaminants.
Maximum Residual Disinfectant Level Goal (MRDLG): The
level of drinking water disinfectant below which there is no
known or expected risk to health. MRDLGs do not reflect the
benefits of the use of disinfectants to control microbial
contaminants.
MFL: Million Fibers per Liter (a measure of asbestos).
Mrem: millirems per year (a measure of radiation absorbed
by the body)
N/A: Not applicable.
NTU: Nephelometric Turbidity Units (a measure of turbidity).
pCi/L: Picocuries per liter (a measure of radioactivity).
ppb: micrograms per liter or parts per billion.
ppm: milligrams per liter or parts per million
ppq: Parts per quadrillion, or picograms per liter (pg/L).
ppt: Parts per trillion, or nanograms per liter (ng/L).
Treatment Technique or TT: A required process intended to
reduce the level of a contaminant in drinking water.

Page 2

PWS #: 2460120
Page 2 of 4
Substance
Unit of
Measure
Year
MCL
Average Level
Detected
Min - Max
Level
Detected
MCLG
In
Compliance
Typical Sources
Disinfectant Byproducts
Haloacetic Acids (HAA5)
ppb
2022
60
19.48
16 - 23.4
0
Yes
By-product of drinking water disinfection.
Total Trihalomethanes
ppb
2022
80
53.48
42.3 - 71
0
Yes
By-product of drinking water disinfection.
Substance
Unit of
Measure
Year
MRDL
Average Level
Detected
Min - Max
Level
Detected
MRDLG
In
Compliance
Typical Sources
Maximum Residual Disinfectant Level
Chlorine Residual
ppm
2022
4.0
3.32
3.14 - 3.59
4.0
Yes
Water additive used to control microbes.
Substance
Unit of
Measure
Year
90th % Value
EPA Action
Level
Results above
Action Level
MCLG
In
Compliance
Typical Sources
Lead and Copper (Regulated at Customers Tap)
Copper
ppm
2021
0.29
1.3
0
1.3
Yes
Corrosion of household plumbing systems, erosion of natural
deposits; leaching from wood preservatives.
Lead
ppb
2021
1.9
15
0
0
Yes
Corrosion of household plumbing systems; erosion of natural
deposits.

Page 3

PWS #: 2460120
Page 3 of 4
Our Water Supply System Received Water From
City of Cedar Park
Water Quality Results are Listed Below
Substance
Unit of
Measure
Year
MCL
Average Level
Detected
Min - Max
Level
Detected
MCLG
In
Compliance
Typical Sources
Unregulated Contaminants
Bromodichloromethane
ppb
2022
N/A
16.0
16 - 16
N/A
Yes
By-product of drinking water disinfection.
Bromoform
ppb
2022
N/A
5.3
5.3 - 5.3
N/A
Yes
By-product of drinking water disinfection.
Chloroform
ppb
2022
N/A
23.0
23 - 23
N/A
Yes
By-product of drinking water disinfection.
Dibromochloromethane
ppb
2022
N/A
14.0
14 - 14
N/A
Yes
By-product of drinking water disinfection.
Unregulated contaminants are those for which EPA has not established drinking water standards. The purpose of unregulated contaminant monitoring is to assist EPA in determining the occurrence of
unregulated contaminants in drinking water and whether future regulation is warranted.
Inorganic Contaminants (Regulated at the Water Plant)
Arsenic
ppb
2022
10
2.3
2.3 - 2.3
0
Yes
Erosion of natural deposits; runoff from orchards; runoff from
glass, and electronics production wastes.
Barium
ppm
2022
2
0.06
0.06 - 0.06
2
Yes
Discharge of drilling wastes; discharge from metal refineries;
erosion of natural deposits.
Fluoride
ppm
2022
4
0.62
0.62 - 0.62
4
Yes
Erosion of natural deposits; water additive which promotes
strong teeth; discharge from fertilizer and aluminum factories.
Nitrate
ppm
2022
10
0.08
0 - 0.11
10
Yes
Runoff from fertilizer use; leaching from septic tanks, sewage;
erosion of natural deposits.
Turbidity
Turbidity has no health effects. However, turbidity can interfere with disinfection and provide a medium for microbial growth. Turbidity may indicate the presence of disease-causing organisms. These organisms
include bacteria, viruses, and parasites that can cause symptoms such as nausea, cramps, diarrhea and associated headaches.
Level Detected
Limit (Treatment Technique)
In Compliance
Likely Source of Contamination
Highest single
measurement
0.3 NTU
1 NTU
Yes
Soil runoff.
Lowest monthly % meeting
limit
100%
0.3 NTU
Yes
Soil runoff.

Page 4

PWS #: 2460120
Page 4 of 4
Our Water Supply System Received Water From
Brushy Creek Regional Utility Authority
Water Quality Results are Listed Below
Substance
Unit of
Measure
Year
MCL
Average Level
Detected
Min - Max
Level
Detected
MCLG
In
Compliance
Typical Sources
Unregulated Contaminants
Bromodichloromethane
ppb
2022
N/A
6.6
6.6 - 6.6
N/A
Yes
By-product of drinking water disinfection.
Bromoform
ppb
2022
N/A
4.8
4.8 - 4.8
N/A
Yes
By-product of drinking water disinfection.
Chloroform
ppb
2022
N/A
2.7
2.7 - 2.7
N/A
Yes
By-product of drinking water disinfection.
Dibromochloromethane
ppb
2022
N/A
9.9
9.9 - 9.9
N/A
Yes
By-product of drinking water disinfection.
Unregulated contaminants are those for which EPA has not established drinking water standards. The purpose of unregulated contaminant monitoring is to assist EPA in determining the occurrence of
unregulated contaminants in drinking water and whether future regulation is warranted.
Inorganic Contaminants (Regulated at the Water Plant)
Barium
ppm
2022
2
0.06
0.06 - 0.06
2
Yes
Discharge of drilling wastes; discharge from metal refineries;
erosion of natural deposits.
Cyanide
ppb
2022
200
100.0
100 - 100
200
Yes
Discharge from plastic and fertilizer factories; discharge from
steel/metal factories.
Fluoride
ppm
2022
4
0.61
0.61 - 0.61
4
Yes
Erosion of natural deposits; water additive which promotes
strong teeth; discharge from fertilizer and aluminum factories.
Nitrate
ppm
2022
10
0.12
0.08 - 0.16
10
Yes
Runoff from fertilizer use; leaching from septic tanks, sewage;
erosion of natural deposits.
Turbidity
Turbidity has no health effects. However, turbidity can interfere with disinfection and provide a medium for microbial growth. Turbidity may indicate the presence of disease-causing organisms. These organisms
include bacteria, viruses, and parasites that can cause symptoms such as nausea, cramps, diarrhea and associated headaches.
Level Detected
Limit (Treatment Technique)
In Compliance
Likely Source of Contamination
Highest single
measurement
0.06 NTU
1 NTU
Yes
Soil runoff.
Lowest monthly % meeting
limit
100%
0.3 NTU
Yes
Soil runoff.
* All levels detected were below the MCLs.